Continuous
over-temperature
condition
Do
contactors pull out
at setpoint?
Correct
temperature
setpoint?
Yes
Properly set
temperature
setpoint
Yes
Plug probe end into RJ45 pigtail
(not supplied). Check ohms
across terminals 1and 4
(see diagrams 1 & 2). Compare
this with the ohms the thermistor
should supply for the actual
temperature in the tank
Do ohms
match?
Yes
Replace probe
No
OK?
Contact factory
Yes
No
Is there
208/240V across
terminals of J5 on the
control board as shown
in the
diagram 3?
J5
No
Replace contactor
No
Replace control
board
No
Any or all buttons
do not work, but
display is
operational.
Re-seat ribbon
cable from display
to control board
No
Replace digital
display
OK?
Replace control
board
No
OK?
Verify that the
display is properly
seated to the base
and that the
buttons click when
pressed.
No
OK?
Individual display
elements do not
work or unusual
characters are
displayed
Re-seat ribbon
cable from display
to control board. Be
sure ribon cable is
not reversed.
No
Replace digital
display
OK?
Replace control
board
No
OK?
Diagram 3
White
Red
Yellow
For 1 contactor:
check voltage across 1 & 4
For 2 contactor:
check voltage across 1 & 3 and 1 & 4
Black
Is there
zero amp draw when the
contactors drop out at
setpoint?
Yes
No
Are configuration
settings set properly,
per Section III, Para.
4?
Yes
1
2
3
4