Hubbell Electric Heater Company J User Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 31
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
14
kW Volt Ph
Unit
Amp
Draw
Branch
Amp Draw
Phase-Phase
Resistance
(Ohms)
Min. Feed
Breaker or
Fuse Size
Internal
Power Wire
Size
Element
Jumper
Wire Size
Copper Power
Feed Wire Size
Conduit
Size
Diagram
208 1 115.4 38.5 1.8 145 10 12 1/0 1¼" 3A
208 3 66.6 66.6 3.6 85 8 10 4 1" 13(NT)
240 1 100.0 33.3 2.4 130 12 12 1 1¼" 3A
240 3 57.7 57.7 4.8 75 8 10 4 1" 13(NT)
480 3 28.9 28.9 19.2 40 12 12 8 ½" 13(WT)
600 3 22.6 22.6 30.6 30 12 12 10 ½" 15
208 1 130.0 43.3 1.6 165 10 12 2/0 1½" 6A
208 3 74.9 37.5 3.2 95 10 12 3 1" 12(NCB)
240 1 112.5 37.5 2.1 145 10 12 1/0 1¼" 3A
240 3 65.0 65.0 4.3 85 8 10 4 1" 13(NT)
480 3 32.5 32.5 17.1 45 12 12 8 ½" 13(WT)
600 3 27.2 27.2 25.5 35 12 12 8 ½" 15
208 1 144.2 48.1 1.4 185 8 10 3/0 1½" 6A
208 3 83.3 41.6 2.9 105 10 12 2 1" 12(NCB)
240 1 125.0 41.7 1.9 160 10 12 2/0 1½" 6A
240 3 72.2 36.1 3.8 95 10 12 3 1" 12(NCB)
480 3 36.1 36.1 15.4 50 10 12 8 ½" 13(WT)
600 3 29.4 29.4 23.6 40 12 12 8 ½" 15
208 1 173.1 57.7 1.2 220 8 10 4/0 2" 6A
208 3 99.9 50.0 2.4 125 8 10 1 1¼" 12(NCB)
240 1 150.0 50.0 1.6 190 8 10 3/0 1½" 6A
240 3 86.6 43.3 3.2 110 10 12 2 1" 12(NCB)
480 3 43.3 43.3 12.8 55 10 12 6 ¾" 13(WT)
600 3 36.2 36.2 19.1 50 10 12 8 ½" 15
208 1 187.5 62.5 1.1 235 8 10 250 2" 6A
208 3 108.3 54.1 2.2 140 8 10 1/0 1¼" 12(NCB)
240 1 162.5 54.2 1.5 205 8 10 4/0 1½" 6A
240 3 93.8 46.9 3.0 120 10 12 1 1" 12(NCB)
480 3 46.9 46.9 11.8 60 8 10 6 ¾" 13(WT)
600 3 36.2 36.2 19.1 50 10 12 8 ¾" 15
208 1 195.0 65.0 1.1 245 8 10 250 2" 6A
208 3 112.6 56.3 2.1 145 8 10 1/0 1¼" 12(NCB)
240 1 168.8 56.3 1.4 215 8 10 250 1½" 6A
240 3 97.4 48.7 2.8 125 10 12 1 1" 12(NCB)
480 3 48.7 48.7 11.4 65 8 10 4 ¾" 13(WT)
600 3 36.2 36.2 19.1 50 10 12 8 ¾" 15
208 3 119.1 59.5 1.9 150 8 10 2/0 1¼" 12(NCB)
240 1 187.5 62.5 1.3 235 8 10 250 2" 6A
240 3 108.3 54.1 2.6 140 8 10 1/0 1¼" 12(NCB)
480 3 54.1 54.1 10.2 70 8 10 4 ¾" 13(WT)
600 3 42.2 42.2 16.4 55 10 12 6 ¾" 15
208 3 149.9 74.9 1.6 190 6 8 3/0 1½" 12
240 3 129.9 65.0 2.1 165 8 10 2/0 1½" 12
480 3 65.0 65.0 8.5 85 8 10 4 1" 13(WT)
600 3 54.3 54.3 12.8 70 8 10 4 1" 15
208 3 159.9 79.9 1.5 200 6 8 4/0 1½" 12
240 3 140.7 70.4 2.0 180 6 8 2/0 1½" 12
480 3 70.4 35.2 7.9 90 12 12 3 1" 12(WT)
600 3 54.3 54.3 12.8 70 8 10 4 1" 15
58.5
24
27
30
36
39
40.5
45
54
Notes:
1. Power feed wire sizing is based on using 75°C Cu THHN wire with feeder branch protection rated at 125%.
2. Internal wire sizing is based on using 200°C SEW-2 or PTFE wiring in a raceway with an ambient temperature up to 60°C.
3. For information on 380V, 415V, or 440V models reference the supplied drawing or contact the factory.
4. Normal phase-to-phase resistance tolerance is ±5%.
5. 480-volt and 600-volt phase-to-phase resistance values are shown with the transformer disconnected.
6. For 575V models, multiply the kW rating of the 600V model by a de-rating factor of 0.92 to get the actual rating for 575V.
7. For models manufactured prior to June 24, 2005, that utilize wiring diagrams 3, 5, 6, 7(NT), 7(WT), or 11 please contact the factory for wiring diagrams.